F-Gas Refrigerant Containment & Leak Testing

Last reviewed: August 2026

What is it?

Statutory containment rules regulating fluorinated greenhouse gases (HFCs, HFOs) used in commercial chillers, VRF/VRV air conditioning systems, and heat pumps to curb atmospheric global warming emissions.

Who is responsible?

The System Operator (the entity exercising actual operational control over the cooling/heating equipment).

What needs to happen?

  • 01Calculate the Global Warming Potential (GWP) and carbon dioxide equivalent (t CO2e) charge for each stationary refrigeration/air conditioning system.
  • 02Conduct mandatory leak checks by certified personnel (F-Gas Category 1 certified technicians).
  • 03Repair any detected leaks within 14 days and conduct a follow-up verification test within 1 month.
  • 04Maintain an on-site or digital F-Gas register logging refrigerant added, recovered, and decommissioned.

How often?

Systems ≥5 t CO2e: at least every 12 months (24 months if fitted with automatic leak detection). ≥50 t CO2e: every 6 months. ≥500 t CO2e: every 3 months.

Source: Fluorinated Greenhouse Gases Regulations 2015 & Regulation (EU) 2024/573.

What evidence should I hold?

Comprehensive F-Gas system asset register with charge weight (kg) and t CO2e calculations
Leak test inspection records signed by Refcom / F-Gas certified engineers
Waste transfer/recovery consignment notes for recovered refrigerant gases
What happens if it is missed?

The Environment Agency (EA) issues Civil Sanction Enforcement Notices and variable monetary penalties for failure to maintain F-Gas records or failure to repair leaks within 14 days.

Official Sources

Department for Environment, Food & Rural Affairs (DEFRA) and Environment Agency · Last updated April 2024

F-Gas in refrigeration, air conditioning and heat pump systems: UK guidance

Official Source

EntireFM Practical Guidance

EntireFM notes that under the latest refrigerant phase-down schedules, legacy high-GWP refrigerants (R404A, R410A) face supply constraints and sharp price escalation. Factor R32 or ultra-low GWP R290/R1234ze retrofit planning into your 5-year capital replacement plan.

EntireFM practical interpretation is separate from official statutory guidance. Always verify against primary legislation.