The FM Statutory Compliance Calendar What to Check and When

A complete guide mapping out the core statutory and recommended facilities maintenance activities that must be performed throughout the calendar year.

Editorial Team
|6 min read|Updated March 2024

Managing FM compliance across a commercial building involves tracking dozens of statutory and recommended maintenance activities — each with different legal frequencies, different responsible engineers, and different record-keeping requirements. This guide maps out the full compliance calendar year: what needs to happen monthly, quarterly, six-monthly, and annually — and what the consequences are if it doesn't.

Statutory Legislation

SFG20 / BS Standards / UK Health & Safety Legislation

SFG20 provides the benchmark maintenance frequencies for all building services assets. Many of these are also statutory requirements — legal obligations with enforcement consequences if missed.

Benchmark
12+

Statutory checks required per building annually

Industry Average
Benchmark
Monthly

Most frequent requirement — fire alarm & emergency lighting

Industry Average
Benchmark
5 Years

Maximum EICR interval for commercial premises

Industry Average

Monthly Compliance Activities

The highest frequency statutory checks typically involve fire prevention routines and preliminary water hygiene surveillance.

ActivityStandardStatutory?Evidence Required
Fire alarm weekly testBS 5839-1YesLogbook entry — date, tester, result
Emergency lighting functional testBS 5266-1YesLogbook entry — all units checked
Legionella temperature monitoring (sentinel outlets)L8 ACoPYesTemperature log sheet
Flushing of infrequently used outletsHSG274RecommendedFlushing record
General building walkround inspectionHealth & Safety at Work Act 1974RecommendedInspection record

Quarterly Compliance Activities

Quarterly activities tend to pivot around intensive specialist inspections testing deeper layers of safety.

ActivityStandardStatutory?Evidence Required
Fire alarm full system inspectionBS 5839-1YesEngineer certificate
Legionella temperature monitoring (all outlets)L8 ACoPYesFull temperature log
Showerhead cleaning and descalingL8 ACoPYesService record
Cooling tower microbiological monitoringHSG274YesLab test results
HVAC filter check and cleanSFG20RecommendedPPM service record

Six-Monthly Activities

Biannual inspections generally affect mechanical items with moving components running constantly such as lifts and ventilation fans.

ActivityStandardStatutory?Evidence Required
Passenger lift thorough examinationLOLER 1998YesLOLER examination report
Dry riser visual inspectionBS 9990YesInspection record
Sprinkler system inspectionBS EN 12845YesEngineer certificate
HVAC full serviceSFG20RecommendedPPM service record

Annual Activities

Annual obligations account for large-scale safety assessments that confirm long-term system integrity.

ActivityStandardStatutory?Evidence Required
Emergency lighting full duration testBS 5266-1YesEngineer certificate
Fire extinguisher serviceBS 5306-3YesService label + certificate
Commercial boiler serviceGas Safety Regs 1998YesGas Safe certificate
Dry riser pressure testBS 9990YesTest certificate
Cold water storage tank inspectionL8 ACoPYesInspection report
Fire risk assessment reviewRRO 2005YesUpdated FRA document
PAT testing reviewIET Code of PracticeRecommendedTest records
Roof and gutter inspectionBuilding maintenance best practiceRecommendedInspection report

Records Are Not Optional

Every activity in this calendar requires documentary evidence. In the event of a Fire Authority inspection, HSE visit, or insurance claim, you must be able to produce all records on demand. 'We did it but didn't write it down' is not an acceptable defence.

Specialist Guidance

Use Our Free Compliance Calendar Tool

Build a personalised compliance calendar for your building in 60 seconds — select your assets and generate a 12-month schedule you can export to Google Calendar or Outlook.

Build My Calendar →
Found this helpful? Share it:
LinkedIn Email

Need Expert FM Support?

Consolidate all compliance checks under one provider. Get a proposal for full assurance.

Key Statistics

  • Frequencies: Monthly to 2-yearly
  • Statutory items: 12+ per building
  • Key standard: SFG20 / BS series
  • Records required: Yes — all items